12 Parameters
SMA Solar Technology AG
104
SCCP-JP-BA-A4-en-12
User Manual
Start time for monitoring of all
groups
7:00 a.m. to
7:00 p.m.
‒
10:00
a.m.
Stop time for monitoring of all
groups
7:00 a.m. to
7:00 p.m.
‒
3:00 p.m.
Ackn
Acknowledge errors
quit
‒
−
ErrLevGr
Sensitivity of error detection for
group
1
Parameter exists for all six
groups
24 Sensitive
50 min ‒ 10%
32
Regular
24 Regular
50 min ‒ 14%
24 Insensitive
50 min ‒ 18%
32 Sensitive
35 min ‒ 10%
32 Regular
35 min ‒ 13%
32 Insensitive
35 min ‒ 16%
64 Sensitive
15 min ‒ 7%
64 Regular
15 min ‒ 9%
64 Insensitive
15 min ‒ 10%
Baud rate
1,200 Bd
Parameter can only be
changed in the operating
state "Stop".
19,200
Bd
4,800 Bd
9,600 Bd
19,200 Bd
38,400 Bd
57,600 Bd
Manages the
Sunny String-Monitors
AutoDetect_SSMU
Searches for all
Sunny String-Monitors
and deletes previously
detected Sunny
String-Monitors
0
DetectSSMURetry
Searches for undetected
Sunny String-Monitors
only
DelAll_SSMU
Deletes all detected
Sunny String-Monitors
Factory
Resets all parameters to
default settings
* To change these parameters, you must enter the installer password.
Name
Description
Value/range
Explanation
Default
value