SMA Solar Technology AG
12 Parameters
User Manual
SCCP-JP-BA-A4-en-12
97
Q-VAr
Reactive power in kVAr − 220 kVAr to +220 kVAr SC 500CP-JP
0 kVAr
− 310 kVAr to +310 kVAr SC 630CP-JP
− 385 kVAr to +385 kVAr SC 800CP-JP
Reactive power in kVAr
in the operating state
"Q at Night"
− 500 kVAr to +500 kVAr SC 500CP-JP
0 kVAr
− 700 kVAr to +700 kVAr SC 630CP-JP
− 880 kVAr to +880 kVAr SC 800CP-JP
Q-VArNom
Reactive power in %
− 100% to 100%
‒
0%
QoDQ-VArNom
Reactive power in % in
the operating state
"Q at Night"
− 100% to 100%
‒
0%
Activates/deactivates
the function
"Q at Night"
Off
Deactivated
Off
On
Activated
QoDDccOffDelay* Delay time until the DC
switchgear opens in the
operating state
"Q at Night"
0 s to 86,400 s
‒
3,600 s
SDLimComSrc***
Selection of the
SDELimit source
CAN
SC-COM interface
UART
UART
Via SMA Net
WCtlHzMod**
Activation of
frequency-dependent
active power limitation
Off
Deactivated
Off
CurveHys
Procedure with hysteresis
Curve
Procedure without
hysteresis
WGra**
Active power change
gradient
1% to 100%
‒
100%
WGraEna**
Activation of the active
power change gradient
Off
Deactivated
On
On
Activated
WGraRecon**
Active power change
gradient after a grid
error
0.017%/s to 100.00%/s ‒
0.166%/s
WGraReconEna** Activation of the
decoupling protection
ramp for reconnection
Off
Deactivated
Off
On
Activated
* This parameter can only be viewed.
** To change this parameter, you must enter the installer password.
*** To view or change this parameter, you must enter the installer password.
Name
Description
Value/range
Explanation
Default
value