SMA
Technologie AG
Appendix B Technical Data
Installation manual
SC-100-13:SE2407
Page 43
SC100 indoor Technical Data
Sunny Central data
Symbol
SC100 indoor
Input data
Max. PV power (recommended)
P
PV
110 kWp
a)
DC voltage range, MPPT
U
DC
450 - 820 V
Max. permissible DC voltage
U
DC, max
900 V / optional 1000
V
Max. permissible DC current
I
DC, max
235 A
Voltage ripple, PV voltage
U
PP
< 3 %
Number of DC inputs / terminal not
secured
3 x positive (120 mm²)
M12 screws
3 x negative (120
mm²) M12 screws
Output data
Nominal AC output power
P
AC
100 kW
Operating grid v/- 10 %
U
AC
400 V
Nominal AC current
I
ACnom
145 A
Grid structure
TT, TN-S, TN-C grid
Operating grid frequency
f
AC
50 Hz - 60 Hz
Harmonic distortion of grid current
K
IAC
< 3 % at nominal
power output
Power factor
cos
0.99
at nominal power
output
Efficiency
per IEC61683
10 % ; 25 % ; 50 % ; 75 % ; 100 %
of P
ACnom
10, 25, 50, 75, 100
94.2 / 96.4 / 96.7 /
96.4 / 96.2 %
Euro ETA
96.2 %
Dimensions and weight