Electrical Connection
SMA Solar Technology AG
50
SSMUS-TUS094511
Technical Description
7.6 Connecting Sunny Central - positive grounding
The Sunny Central may not be connected until the communication and the PV modules have been
connected (see section 6 "Communication connector" (page 29), section 7.2 "Connecting ground"
(page 38)and section 7.4 "Connecting the PV modules - positive grounding" (page 44)).
Technical Data for the Connection to the Sunny Central
Technical Data for the Cables to the Sunny Central
Use 90 °C (194 °F), copper wire for all DC wiring connections to the Sunny Central String-Monitor.
DANGER
Risk of electric shock through reverse voltage from Sunny Central.
Death or serious injuries.
• Disconnect the Sunny Central.
Version 24
Version 32
Version 64
Max. number of output
lines per potential
2
2
2
DC Short Circuit Current
480 A
480 A
512 A
DC Max Continuous
Current
308 A
308 A
328 A
Cables to the Sunny Central
Cable Size
Torque
DC+
350 kcmil
325 in-lb
DC–
350 kcmil
325 in-lb