Operation of the Sunny Central String-Monitor
Technical Description
SSMUS-TUS094511
67
ErrLevGr1 –
ErrLevGr6
Sensitive, Regular,
Insensitive, Customer
Regular
Adjusting the string current
monitoring system.
Here you can set the monitoring
parameters for each individual
group.
Firmware
Firmware version of the Sunny
Central String-Monitor Controller.
This parameter cannot be adjusted.
Firmware2
Kernel version of the Sunny Central
String-Monitor Controller.
This parameter cannot be adjusted.
MoniTmComOff 6.00 – 20.00
15.00
Time at which the daily
communication with the Sunny
Central String-Monitors stops.
The time is entered in 24-hour
format. Hours and minutes are
separated by a dot. E.g., for 6:30
p.m. enter "
18.30
".
MoniTmComOn 6.00 – 20.00
10.00
Time at which the daily
communication with the Sunny
Central String-Monitors starts.
The time is entered in 24-hour
format. Hours and minutes are
separated by a dot. E.g., for 10:30
a.m. enter "
10.30
".
MoniTmGr1Off –
MoniTmGr6Off
7.00 – 19.00
15.00
End of monitoring for the Sunny
Central String-Monitor groups 1 to
6.
These parameters will enable you to
set the monitoring end times for each
separate group.
The time is entered in 24-hour
format. Hours and minutes are
separated by a dot. E.g., for 3:00
p.m. enter "
15.00
".
Name
Adjustment range Default setting
Description