7.2 Connecting ground
The PV modules may not be connected until the communication cables have been connected (see
section 6 "Communication connector" (page 29)).
The Photovoltaic System Grounding shall be installed per the requirements of sections 690.41
through 690.47 of the National Electrical Code, ANSI/NFPA 70 and is the responsibility of the
installer. In Canada, wiring methods shall be per the Canadian Electrical Code Part II.
Use 90 °C (194 °F), copper wire for all wiring connections to the Sunny Central String-Monitor.
B
Negative grounding: Screw terminals for DC+ of the PV generator
Positive grounding: Screw terminals for DC– of the PV generator
Use 90 °C (194 °F) copper wire for all DC wiring connections to the fuse holders.
C
Negative grounding: Screw terminals for DC– of the PV generator
Positive grounding: Screw terminals for DC+ of the PV generator
D
Screw terminals for grounding the PV generator
E
Terminal for grounding the DC cable of the Sunny Central
F
Negative grounding: Terminal for DC+ of the Sunny Central
Positive grounding: Terminal for DC– of the Sunny Central
G
Negative grounding: Terminal for DC– of the Sunny Central
Positive grounding: Terminal for DC+ of the Sunny Central
DANGER
Risk of electric shock when touching the DC cable attached to the PV module.
Death or serious injuries.
Voltage is present in PV modules exposed to light.
• Cover the PV modules.
• Follow all safety precautions of the module manufacturer.