Connecting External Sources
SMA
Solar Technology AG
144
SI2012_2224-TEN082311
Technical Description
The "133.03 GnRmgTm" process value is used to display the remaining time of the generator meter.
Depending on the current request or the phase in which the generator state machine is, the following
times are displayed:
•
Remaining time of Run1h
•
Remaining run time during the warm-up phase (Warm)
•
Remaining minimum run time in operation (Run)
•
Remaining run time during the power-down time (Cool)
•
Remaining stop time after the power down-time has elapsed (Lock)
•
Remaining time in the error state (Fail)
•
Remaining time in the locked error state (FailLock)
13.1.8 Operation Together With Sunny Boys
If the battery is fully charged, the frequency limits the power output of the AC feed-in generators
(Sunny Boys). If the generator is now manually started, for example, the frequency would be
lowered, if required, as the Sunny Island synchronizes with the generator. The AC feed-in generators
(Sunny Boys) would then feed additional energy into the system and possibly overload the batteries.
Information
The recording of autostarts is only reset after the generator has been successfully
connected and the minimum run time has expired or when the locked error state
(FailLock) is disabled.
Information
The error state and the locked error state can be cancelled by confirming the generator
fault ("540.02 GnAck" parameter).
NOTICE!
Damage to devices due to improper installation dimensioning.
When dimensioning your installation, please observe:
PAC
max., Sunny Boy
= 2 x P
AC nom., Sunny Island
•
The maximal AC output of the Sunny Boy inverter connected should not exceed
4.4 kW.