Parameter List Overview
SMA
Solar Technology AG
170
SI2012_2224-TEN082311
Technical Description
231
09
ExtSrc
Grid
Grid
Grid Operation
232# Grid Control
232
01
GdVtgMin
V
189
Minimum grid voltage
232
02
GdVtgMax
V
259.5
Maximum grid voltage
232
03
GdCurNom
A
16
Nominal grid current
232
04
GdFrqNom
Hz
50
Nominal frequency
232
05
GdFrqMin
Hz
47.65
Minimum grid frequency
232
06
GdFrqMax
Hz
50.15
Maximum grid frequency
232
07
GdVldTm
sec
30
minimum time required for grid (voltage
and frequency) to be within permissible
range for connection
232
08
GdMod
GridCharge
GridFeed
GridCharge
Grid interface
232
09
GdRvPwr
W
100
permissible grid reverse power
(effective power)
232
10
GdRvTm
sec
5
permissible time for grid reverse power
232
15
GdAISns
Low,
Medium
standard
High
standard
AI sensitivity
233# Gen Control
233
01
GnVtgMin
V
172.5
Min. generator voltage
233
02
GnVtgMax
V
264.5
Max. generator voltage
233
03
GnCurNom
A
25
Nominal generator current
233
04
GnFrqNom
Hz
50
Nominal generator frequency (at
nominal load)
230V_50HZ = 50
220V_60HZ = 60
depending on the setting in QCG
233
05
GnFrqMin
Hz
44.64
Minimum generator frequency
230V_50HZ = 44.64
220V_60HZ = 50
depending on the setting in QCG
233
06
GnFrqMax
Hz
60
Maximum generator frequency
230V_50HZ = 60
220V_60HZ = 70
depending on the setting in QCG
Menu
nr.
Parame
ter.Nr.
Parameter Name
Range/Unit
Default
value
Description