No.
Name
Description
Value
Explanation
Default
Value
222.09
ChrgVtgEqu
Cell voltage setpoint for
equalization charge in V
(expert mode)
2.30 V to 2.70 V
Off-grid
✖
✓
2.45 V
VRLA, on-grid
✓
✖
2.55 V
FLA, on-grid
✓
✖
2.50 V
222.10
ChrgVtgFlo
Cell voltage setpoint for
float charge in V (expert
mode)
2.20 V to 2.40 V
–
✓
✓
2.25 V
222.11
BatTmpCps
Battery temperature com-
pensation in
mV
/
°C
(ex-
pert mode)
0.0
mV
⁄
°C
to
10.0
mV
⁄
°C
–
✓
✓
4.0
mV
⁄
°C
222.12
AutoEquChrgEna
Automatic equalization
charge (expert mode)
Disable
Disable
✓
✓
Enable
Enable
Enable
222.13
BatChrgVtgMan
Manual setpoint of the
battery charging voltage
with disabled battery
management in V (expert
mode)
41.0 V to 63.0 V
–
✓
✓
54.0 V
223# Protection
No.
Name
Description
Value
Default
Value
223.01
BatPro1TmStr
Start time of battery protection mode level
1 in hh:mm:ss (expert mode)
00:00:00 to
23:59:59
✖
✓
22:00:00
223.02
BatPro1TmStp End time of battery protection mode level
1 in hh:mm:ss (expert mode)
00:00:00 to
23:59:59
✖
✓
06:00:00
223.03
BatPro2TmStr
Start time of battery protection mode lev-
el 2 in hh:mm:ss (expert mode)
00:00:00 to
23:59:59
✖
✓
17:00:00
223.04
BatPro2TmStp End time of battery protection mode level
2 in hh:mm:ss (expert mode)
00:00:00 to
23:59:59
✖
✓
09:00:00
223.05
BatPro1Soc
Battery SOC for protection mode level 1
as % (expert mode)
0% to 70%
✖
✓
20 %
223.06
BatPro2Soc
Battery SOC for protection mode level 2
as % (expert mode)
0% to 70%
✖
✓
15 %
13 Parameters in Sunny Remote Control
SMA Solar Technology AG
Operating Manual
127