No.
Name
Description
Value
Explanation
Default
Value
232.03
GdVtgMax
Upper maximum thresh-
old of line voltage for
voltage monitoring in V
(expert mode, pro-
tected by
SMA Grid Guard)
210.01 InvVt-
gNom to
264.50 V
230 V / 50 Hz
✓
✓ 264.50
V
220 V / 60 Hz
242.00
V
232.04
GdCurNom
Maximum current from
the utility grid in A (ex-
pert mode)
0.0 A to 50.0 A
1 inverter
SI 3.0M / 4.4M (sin-
gle-phase)
✖
✓ 16 A
0.0 A to 50.0 A
1 inverter
SI 6.0H / 8.0H (sin-
gle-phase)
✖
✓ 16 A
0.0 A to 100.0 A 2 inverters
SI 6.0H / 8.0H (sin-
gle-phase)
✖
✓ 16 A
0.0 A to 150.0 A 3 inverters
SI 6.0H / 8.0H (sin-
gle-phase)
✖
✓ 16 A
0.0 A to 50.0 A
3 inverters
SI 3.0M / 4.4M
(three-phase)
✖
✓ 16 A
0.0 A to 50.0 A
3 inverters
SI 6.0H / 8.0H
(three-phase)
✖
✓ 16 A
232.05
GdFrqNom
Nominal grid frequency
in Hz (expert mode,
protected by SMA Grid
Guard)
232.05
GdFrqMin to
232.06
GdFrqMax
230 V / 50 Hz
✓
✓ 50.00
Hz
220 V / 60 Hz
60.00
Hz
232.06
GdFrqMin
Lower minimum thresh-
old of power frequency
for frequency monitor-
ing in Hz (expert mode,
protected by
SMA Grid Guard)
40.00 Hz to
232.04
GdFrqNom
230 V / 50 Hz
✓
✓ 47.50
Hz
220 V / 60 Hz
59.30
Hz
232.07
GdFrqMax
Upper maximum thresh-
old of power frequency
for frequency monitor-
ing in Hz (expert mode,
protected by
SMA Grid Guard)
232.4 GdFrqNo
m to 70.00 Hz
230 V / 50 Hz
✓
✓ 51.50
Hz
220 V / 60 Hz
60.50
Hz
13 Parameters in Sunny Remote Control
SMA Solar Technology AG
Operating Manual
SI30M-44M-60H-80H-BE-en-33
130