No.
Name
Description
Value
Explanation
Default
Value
232.14
GdFrqMinDel
Lower frequency differ-
ence for valid grid con-
nection in Hz (expert
mode, protected by
SMA Grid Guard)
0.00 Hz to
2.50 Hz
‒
✓
✓ 0.02 Hz
232.15
GdFrqMaxDel Upper frequency differ-
ence for valid grid con-
nection in Hz (expert
mode, protected by
SMA Grid Guard)
0.00 Hz to
2.50 Hz
VDE_AR_4105
✓
✓ 1.45 Hz
0.00 Hz
0.20 Hz
230 V / 50 Hz
0.02 Hz
0.00 Hz
0.20 Hz
220 V / 60 Hz
0.02 Hz
232.16
GdAlSns
Sensitivity of the anti-is-
landing detection (ex-
pert mode, protected
by SMA Grid Guard)
Low
Low
✓
✓ Standard
Medium
Medium
Standard
Standard
High
High
232.40
GdRtCurSrc
Place of reactive current
compensation in grid
operation (expert
mode)
External
Sunny Island com-
pensates all reactive
currents.
✓
✖ External
Inverter
Sunny Island does
not compensate reac-
tive currents.
Shared
Sunny Island partially
compensates reactive
currents.
232.41
P-WCtlHzMod Operating mode of ac-
tive power reduction in
case of overfrequency
P(f) (expert mode, pro-
tected by
SMA Grid Guard)
Off
Disable
✓
✓
–
WCtlHz
Enable
232.42
P-HzStr
Difference between
starting frequency and
grid frequency, linear
instantaneous power
gradient configuration
(protected by
SMA Grid Guard)
0.0 Hz to 5.0 Hz
This value defines
how many Hz above
210.02 InvFrqNom
the active power limi-
tation starts.
✓
✖ 0.2 Hz
13 Parameters in Sunny Remote Control
SMA Solar Technology AG
Operating Manual
SI30M-44M-60H-80H-BE-en-33
132