No.
Name
Description
Value
Explanation
Default
Value
232.60
EZATyp
Type of PV system feed-
in (expert mode, pro-
tected by
SMA Grid Guard)
Symmetric
All PV inverters are
three-phase and feed
in symmetrically.
✓
✖
–
Asymmetric
At least one PV in-
verter is single-phase
and feeds in asym-
metrically.
233# Grid Start, for Off-Grid Systems Only
No.
Name
Description
Value
Explanation
Default
Value
233.01
GdSocEna
Enable grid request based
on battery state of charge
(expert mode)
Disable
Disable
✖
✓ Disable
Enable
Enable
233.02
GdSocTm1Str Battery state of charge
limit for connection to the
utility grid in the standard
additional time period
in % (expert mode)
This is the valid threshold
without the additional time
period.
1% to
233.03
GdSocTm1Stp
–
✖
✓ 40 %
233.03
GdSocTm1Stp Battery state of charge
limit for disconnection
from the utility grid in the
standard additional time
period as % (expert
mode)
This is the valid threshold
without the additional time
period.
233.02
GdSocTm1Str
to
95%
–
✖
✓ 80 %
233.04
GdSocTm2Str Battery state of charge
limit for connection to the
utility grid in the additional
time period as % (expert
mode)
1% to
233.05
GdSocTm2Stp
‒
✖
✓ 40 %
233.05
GdSocTm2Stp Battery state of charge
limit for disconnection
from the utility grid in the
additional time period as
% (expert mode)
233.04
GdSocTm2Str
to
95%
‒
✖
✓ 80 %
13 Parameters in Sunny Remote Control
SMA Solar Technology AG
Operating Manual
135
SI30M-44M-60H-80H-BE-en-33