No.
Name
Description
Value
Explanation
Default
Value
234.03
GnCurNom
Nominal generator cur-
rent in A
0.0 A to 50.0 A
1 Sunny Island
✖
✓ 16.0 A
0.0 A to 100.0 A
Two Sunny Island
inverters, parallel
16.0 A
0.0 A to 150.0 A
Three Sunny Is-
land inverters,
parallel
16.0 A
0.0 A to 50.0 A
Three-phase
16.0 A
0.0 A to 80.0 A
Multicluster-Box 6
60.0 A
0.0 A to 160.0 A
Multicluster-Box
12 (MC-
BOX-12.3)
160.0 A
0.0 A to 200.0 A
Multicluster-Box
12 (MC-
BOX-12.3-20)
200.0 A
0.0 A to 500.0 A
Multicluster-Box
36
435.0 A
234.04
GnFrqNom
Nominal generator fre-
quency under nominal
load in Hz (expert mode)
234.05 GnFrqMin t
o
234.06 GnFrqMax
230 V / 50 Hz
✖
✓ 50.00 Hz
220 V / 60 Hz
60.00 Hz
234.05
GnFrqMin
Lower minimum threshold
of generator frequency
for frequency monitoring
in Hz (expert mode)
40.00 Hz to
234.04 GnFrqNom
230 V / 50 Hz
✖
✓ 44.64 Hz
50.00 Hz to
234.04 GnFrqNom
220 V / 60 Hz
50.00 Hz
234.06
GnFrqMax
Upper maximum thresh-
old of generator fre-
quency for frequency
monitoring in Hz (expert
mode, protected by
SMA Grid Guard)
234.04 GnFrqNom
to 70.00 Hz
230 V / 50 Hz
✖
✓ 60.00 Hz
220 V / 60 Hz
70.00 Hz
234.07
GnStrMod
Generator interface
Manual
Manual
✖
✓ Autostart
Autostart
Automatic
234.08
GnOpTmMin Minimum run time of gen-
erator in minutes
0 min to 360 min
‒
✖
✓ 15 min
234.09
GnStpTmMin Minimum stop time of the
generator in minutes
0 min to 360 min
‒
✖
✓ 15 min
234.10
GnCoolTm
Cooling time of the gen-
erator in minutes
0 min to 60 min
‒
✖
✓ 5 min