235# Gen Start
No.
Name
Description
Value
Explanation
Default
Value
235.01
GnAutoEna
Automatic restart of gen-
erator in the event of dis-
turbance
Off
Disable
✖
✓ On
On
Enable
235.02
GnAutoStr
Number of attempts to
carry out automatic
restart of generator (ex-
pert mode)
0 to 10
‒
✖
✓ 3
235.03
GnSocTm1Str
Battery state of charge
limit for generator re-
quest in the standard ad-
ditional time period as %
This is the valid threshold
without the additional
time period.
1% to
235.04
GnSocTm1Stp
‒
✖
✓ 40 %
235.04
GnSocTm1Stp
Battery state of charge
limit for end of generator
request in the standard
additional time period as
%
This is the valid threshold
without the additional
time period.
235.03
GnSocTm1Str
to
95%
‒
✖
✓ 80 %
235.05
GnSocTm2Str
Battery state of charge
limit for generator re-
quest in additional time
period as %
1% to
235.06
GnSocTm2Stp
‒
✖
✓ 40 %
235.06
GnSocTm2Stp
Battery state of charge
limit for end of generator
request in the additional
time period as %
235.05
GnSocTm2Str
to
95%
‒
✖
✓ 80 %
235.07
GnTm1Str
Start time of the standard
additional time period
for generator request in
hh:mm:ss; corresponds to
the end time of the addi-
tional time period
00:00:00 to
23:59:59
‒
✖
✓ 00:00:00
235.08
GnTm2Str
Start time of additional
time period for generator
request in hh:mm:ss
00:00:00 to
23:59:59
‒
✖
✓ 00:00:00
235.09
GnPwrEna
Generator request based
on power (expert mode)
Disable
Disable
✖
✓ Enable
Enable
Enable
13 Parameters in Sunny Remote Control
SMA Solar Technology AG
Operating Manual
139
SI30M-44M-60H-80H-BE-en-33
Summary of Contents for SUNNY ISLAND 3.0M