No.
Name
Description
Value
Explanation
Default
Value
235.10
GnPwrStr
Load limit: Generator
start for generator re-
quest based on power in-
kW (expert mode)
235.11
GnPwrStp
to
300.0 kW
–
✖
✓ 4.0 kW
235.11
GnPwrStp
Load limit: Generator
shutdown for end of gen-
erator request based on
power in kW (expert
mode)
0.0 kW to
235.10
GnPwrStr
–
✖
✓ 2.0 kW
235.12
GnPwrAvgTm
Averaging time for load-
dependent generator re-
quest based on power
in s (expert mode)
1 s to 900 s
‒
✖
✓ 60 s
235.13
GnTmOpEna
Time-controlled genera-
tor operation
Disable
Disable
✖
✓ Disable
Enable
Enable
235.14
GnTmOpStrDt
Start date for time-con-
trolled generator opera-
tion in dd.mm.yyyy
‒
‒
✖
✓ 2011-01-
01
235.15
GnTmOpStrTm
Time at the start of time-
controlled generator op-
eration in hh:mm:ss
00:00:00 to
23:59:59
‒
✖
✓ 00:00:00
235.16
GnTmOpRnDur Run time for time-con-
trolled generator opera-
tion in hh:mm:ss
00:00:00 to
99:59:00
‒
✖
✓ 00:00:00
235.17
GnTmOpCyc
Repeat cycle for time-
controlled generator op-
eration
Single
Once
✖
✓ Single
Daily
Daily
Weekly
Weekly
235.18
GnStrChrgMod Generator request in
configured charge mode
(expert mode)
Off
Off
✖
✓ Both
Full
Full charge
Equal
Equalization
charge
Both
Full and equal-
ization charge
235.19
GnStrDigIn
Generator request in re-
sponse to signal on acti-
vated digital input (ex-
pert mode)
Disable
Disable
✖
✓ Disable
Enable
Enable
13 Parameters in Sunny Remote Control
SMA Solar Technology AG
Operating Manual
SI30M-44M-60H-80H-BE-en-33
140