241.01 Rly1Op: Operating mode of the multifunction relay 1
Value
Explanation
GndSwt
Triggering of the grounding in the battery backup system
GriRdtSwt
Triggering of redundant contactor for grid disconnection in the battery backup system
242# Load
No.
Name
Description
Value
Default
Value
242.01
Lod1SocTm1Str
Battery state of charge limit for start of
load shedding 1 in the standard addi-
tional time period as %
This is the valid threshold without the
additional time period.
1% to
242.02
Lod1SocTm1Stp
✓
✓
30 %
242.02
Lod1SocTm1Stp Battery state of charge limit for end of
load shedding 1 in the standard addi-
tional time period as %
This is the valid threshold without the
additional time period.
242.01
Lod1SocTm1Str
to 90%
✓
✓
50 %
242.03
Lod1SocTm2Str
Battery state of charge limit for start of
load shedding 1 in additional time pe-
riod as %
1% to
242.04
Lod1SocTm2Stp
✓
✓
30 %
242.04
Lod1SocTm2Stp Battery state of charge limit for end of
load shedding stop in additional time
period as %
242.03
Lod1SocTm2Str
to 90%
✓
✓
50 %
242.05
Lod1Tm1Str
Start time of the standard additional
time period for load shedding 1 in
hh:mm:ss; corresponds to the end time
of the additional time period
00:00:00 to 23:59:59
✓
✓
–
242.06
Lod1Tm2Str
Start time of the additional time period
for load shedding 1 in hh:mm:ss
00:00:00 to 23:59:59
✓
✓
–
242.07
Lod2SocTm1Str
Battery state of charge limit for start of
load shedding 2 in the standard addi-
tional time period as %
This is the valid threshold without the
additional time period.
1% to
242.08
Lod2SocTm1Stp
✓
✓
30 %
242.08
Lod2SocTm1Stp Battery state of charge limit for end of
load shedding 2 in the standard addi-
tional time period as %
This is the valid threshold without the
additional time period.
242.07
Lod2SocTm1Str
to 90%
✓
✓
50 %
242.09
Lod2SocTm2Str
Battery state of charge limit for start of
load shedding 2 in the standard addi-
tional time period as %
1% to
242.10
Lod2SocTm2Stp
✓
✓
30 %
13 Parameters in Sunny Remote Control
SMA Solar Technology AG
Operating Manual
143
SI30M-44M-60H-80H-BE-en-33
Summary of Contents for SUNNY ISLAND 3.0M
Page 163: ......
Page 164: ...www SMA Solar com...