No.
Name
Description
Value
Explanation
Default
Value
261.04
SlfCsmpSpnt
Specification of the
control target at ac-
tive self-consumption
in W*
≤ 0 W
Negative value: grid feed-in
✓
✖ 0 W
0 W
No grid feed-in and pur-
chased electricity
≥0 W
Positive value: purchased
electricity
261.05
SlfCsm-
pLodShed
Activation of load
shedding during
self-consumption.*
Disable
Load shedding during self-
consumption is deactivated.
✓
✖ Enable
Enable
Load shedding during self-
consumption is activated.
* The parameter is visible until firmware version 3.5 of the Sunny Island. Firmware version 3.5 of Sunny Island can only be used in
multicluster systems with the Multicluster-Box 12 of device type MC-BOX-12.3-20.
262# BatUsage
No.
Name
Description
Value
Explanation
Default
Value
262.01
ProtResSOC
Lower limit of the
deep-discharge pro-
tection range for dis-
connection (%) of
the battery capacity
(expert mode)
10% to 20%
Lead-acid batteries
✓
✖ 10 %
3% to 20%
Lithium-ion batteries
✓
✖ 3 %
262.02
BatResSOC
Minimum width of
the deep-discharge
protection range (%)
of the battery ca-
pacity (expert
mode)
2% to 50%
Lithium-ion battery, self-con-
sumption only
✓
✖ 2 %
Lithium-ion battery, battery
backup system
✓
✖ 10 %
Lead-acid battery, self-con-
sumption only
✓
✖ 30 %
Lead-acid battery, battery
backup system
✓
✖ 5 %
262.03
BUResSOC
Minimum width of
the backup power
supply range on the
longest day of the
year as a percent-
age of the battery
capacity (expert
mode)
0% to 100%
–
✓
✖ 0 %
13 Parameters in Sunny Remote Control
SMA Solar Technology AG
Operating Manual
SI30M-44M-60H-80H-BE-en-33
148
Summary of Contents for SUNNY ISLAND 3.0M
Page 163: ......
Page 164: ...www SMA Solar com...