No.
Name
Level Cause
Corrective measures
F 158 VtgOnAC1Det
2
Voltage at AC connection
Line conductor L1
: The master
has measured an undesired volt-
age at connection
AC1
.
A bypass switch may have bridged the
internal transfer relay.
• Ensure that the bypass switch is in
the position for operation with the
Sunny Island.
• Ensure that the bypass switch is in
the position for operation with the
Sunny Island.
An external energy source (e.g., genera-
tor) may have been connected to the
connection
AC1
.
• Disconnect external energy source
from connection
AC1
and connect
to connection
AC2
(see the
Sunny Island inverter installation
manual).
W 159 VtgOnAC1DetSlv1
1
Voltage at AC connection
Line conductor L2
: slave 1 has
measured an undesired voltage
at connection
AC1
.
W 160 VtgOnAC1DetSlv2
1
Voltage at AC connection
Line conductor L3
: slave 2 has
measured an undesired voltage
at connection
AC1
.
F 162 OvrCurDet
2
Too much current is flowing
through the
DC
connection of
the master.
• Reduce the power of the loads.
W 163 OvrCurDetSlv1
1
Too much current is flowing
through the
DC
connection of
slave 1.
W 164 OvrCurDetSlv2
1
Too much current is flowing
through the
DC
connection of
slave 2.
F 166 Overload5min
3
The device at L1 (Master) has
been loaded over its five-minute
rated capacity.
• Reduce the power of the loads.
W 167 Overload5minSlv1
1
The device at L2 (slave 1) has
been loaded over its five-minute
rated capacity.
W 168 Overload5minSlv2
1
The device at L3 (slave 2) has
been loaded over its five-minute
rated capacity.
10 Troubleshooting
SMA Solar Technology AG
Operating Manual
55