No.
Name
Level Cause
Corrective measures
F 179 RetryConFail
4
The pre-fuse
F104.1
in the Mul-
ticluster-Box is open. The master
in the main cluster detects a sup-
ply voltage at
ExtVtg
and tries
to switch to line conductor L1 in
the multicluster system. At line
conductor L1 an anti-islanding
error occurs due to the open
pre-fuse.
• Reactivate the pre-fuse.
• Check the voltage supply at
terminal AC2 of the master in the
main cluster.
W 180 RetryConFailS1
4
The pre-fuse
F104.2
in the Mul-
ticluster-Box is open. The master
in the main cluster detects a sup-
ply voltage at
ExtVtg
and tries
to switch to Phase L2 in the mul-
ticluster system. At line conduc-
tor L2 an anti-islanding error oc-
curs due to the open pre-fuse.
W 181 RetryConFailS2
4
The pre-fuse
F104.3
in the Mul-
ticluster-Box is open. The master
in the main cluster detects a sup-
ply voltage at
ExtVtg
and tries
to switch to line conductor L3 in
the multicluster system. At line
conductor L3 an anti-islanding
error occurs due to the open
pre-fuse.
10.5.2 Battery Category (2xx)
No.
Name
Level Cause
Corrective measures
F 201 VBATMAX
2
Measuring range of battery
voltage exceeded in device
at L1
: Battery voltage at the
master is above the permissible
measurement range.
• Check whether the value of the
parameter
120.02 BatVtg
is
above 65.0 V. If the value is above
65.0 V, check the settings of the DC
sources and ensure that the battery
capacity is sufficient. When doing
so, bear in mind the technical data
for the battery at the
DC
connection
(see the Sunny Island inverter
installation manual).
• Ensure that the DC sources are
correctly connected and
configured.
W 202 VBATMAXSL1
1
Measuring range of battery
voltage exceeded in device
at L2
: Battery voltage at slave 1
is above the permissible mea-
surement range.
W 203 VBATMAXSL2
1
Measuring range of battery
voltage exceeded in device
at L3
: Battery voltage at slave 2
is above the permissible mea-
surement range.
10 Troubleshooting
SMA Solar Technology AG
Operating Manual
57
SI30M-44M-60H-80H-BE-en-33
Summary of Contents for SUNNY ISLAND 3.0M