No.
Name
Level Cause
Corrective measures
F 704 Calib
4
Invalid Calibration in DSP
:
The system has not calibrated.
• Contact the Service (see Section 16
W 705 TimeOut
1
Watchdog DSP
: The watchdog
of the signal processor of the
master has tripped.
• Contact the Service, if required (see
Section 16 "Contact", page 161).
F 706 TimeOut
4
Frequent watchdog fault
: The
watchdog of the signal proces-
sor of the master has tripped
several times.
• Contact the Service (see Section 16
W 707 TimeOutSlv1
1
Watchdog meter on slave 1
elapsed (watchdog tripped sev-
eral times in succession)
W 708 TimeOutSlv2
1
Watchdog meter on slave 2
elapsed (watchdog tripped sev-
eral times in succession).
F 710 AutoStrCnt
4
Autostart meter elapsed in the
device at L1 (several autostarts
in succession).
• Ensure that the parameter
250.01
AutoStr
is set to
3
.
• Read off the pending and logged
warnings and errors and eliminate
the causes.
W 713 TimeOut
1
Watchdog OCU
: The watch-
dog of the operation control unit
has tripped.
• Contact the Service, if required (see
Section 16 "Contact", page 161).
W 715 MMCUpdFail
1
The update cannot be carried
out. The type or format of the
SD memory card is not sup-
ported.
Copy the update file to an SD memory
card with maximum 2 GB and with
FAT-16 format.
F 716 VBATMIN
2
Measuring range of battery
voltage exceeded in device
at L1
: Battery voltage at the
master is below the permissible
measurement range.
• Disconnect the DC loads and
charge the battery.
The usable battery capacity may be too
small, e.g., due to aging. If a load with
high power connects, the battery voltage
collapses.
• If DC loads are installed in the
system, install load shedding for DC
loads.
• Ensure that all battery cells are
functional.
W 717 VBATMINSL1
1
Measuring range of battery
voltage exceeded in device
at L2
: Battery voltage at slave 1
is below the permissible mea-
surement range.
W 718 VBATMINSL2
1
Measuring range of battery
voltage exceeded in device
at L3
: Battery voltage at slave 2
is below the permissible mea-
surement range.
10 Troubleshooting
SMA Solar Technology AG
Operating Manual
69
SI30M-44M-60H-80H-BE-en-33
Summary of Contents for SUNNY ISLAND 3.0M
Page 163: ......