No.
Name
Level Cause
Corrective measures
W 885 Sic4TmpLo
1
Sensor error (or undertem-
perature) for the PV charge
controller 4 charger temper-
ature
: Sunny Island Charger 4
reports battery undertempera-
ture.
• Set the Sunny Island Charger to the
operating mode "SMA
operation" (see the Sunny Island
Charger charge controller
installation manual).
W 886 Sic4TmpHI
1
PV charge controller 4 de-
vice overtemperature
: Sun-
ny Island Charger 4 reports bat-
tery overtemperature.
W 887 Sic4ComLoss
1
No communication with DC
charger for more than 24 h
– PV charge controller 4
: Last
communication with the Sun-
ny Island Charger 4 was more
than 24 hours ago.
• Ensure that undamaged CAT5e
cables are used for communication
and that the cables are plugged in
correctly.
• Ensure that the configuration of the
Sunny Island Charger charge
controller with the DIP switches is
correct.
• Ensure that the communication
interfaces are correctly inserted in
the Sunny Island.
W 890 BoxMeas
2
Voltage or current measurement
interferences at external mea-
surement point of the AC sub-
distribution (Multicluster-Box) at
line conductor L1 (Master)
• Ensure that the control and
measuring cable between the
Multicluster-Box and the
corresponding Sunny Island of the
main cluster is correctly inserted.
When doing so, observe the correct
sequence of the Multicluster-Box
connections to the Sunny Island
inverters (see the Sunny Island
inverter installation manual and the
Multicluster-Box documentation).
W 891 BoxMeasSlv1
2
Voltage or current measurement
interferences at external mea-
surement point of the AC sub-
distribution (Multicluster-Box) at
line conductor L2 (slave 1)
W 892 BoxMeasSlv2
2
Voltage or current measurement
interferences at external mea-
surement point of the AC sub-
distribution (Multicluster-Box) at
line conductor L3 (slave 2)
F 894 BoxQ10LdScFail
4
Q10 error
: The voltage supply
of
Q10
/
Q110
fails due to a
short circuit in the stand-alone
grid.
• Eliminate the short circuit.
10 Troubleshooting
SMA Solar Technology AG
Operating Manual
SI30M-44M-60H-80H-BE-en-33
82
Summary of Contents for SUNNY ISLAND 3.0M
Page 163: ......