No.
Name
Level Cause
Corrective measures
W 941 XW06DcHiTmpC
1
Warning via SiCom: Battery
overtemperature in charge
mode
• Eliminating the error cause in the
external battery management
system (see battery manufacturer's
documentation).
W 942 XA07DcLoTmpC
1
Warning via SiCom: Battery un-
dertemperature in charge mode
W 943 XW08DcHiCur
1
Warning via SiCom: battery
charging current too high
• Eliminating the error cause in the
external battery management
system (see battery manufacturer's
documentation).
W 944 Warning via SiCom:
battery charging cur-
rent in charge mode
too high
1
Warning via SiCom: battery
charging current in charge
mode too high
W 945 XW10Contact
1
Warning via SiCom: error in the
battery
• Eliminating the error cause in the
external battery management
system (see battery manufacturer's
documentation).
W 946 XW11Short
1
Warning via SiCom: short circuit
• Eliminating the error cause in the
external battery management
system (see battery manufacturer's
documentation).
W 947 XW12Bms
1
Warning via SiCom: internal er-
ror in battery management
• Eliminating the error cause in the
external battery management
system (see battery manufacturer's
documentation).
W 948 XW13CellBal
1
Warning via SiCom: different
state of charge of the battery
cells
• Eliminating the error cause in the
external battery management
system (see battery manufacturer's
documentation).
w 949 XW14PackBal
1
Warning via SiCom: Reserved
• Eliminating the error cause in the
external battery management
system (see battery manufacturer's
documentation).
W 951 XW16Generator
1
Warning via SiCom: Error in the
generator
• Eliminating the error cause in the
external battery management
system (see battery manufacturer's
documentation).
F 952 ExtBMSTimeout
3
The timeout monitoring system
of the battery management has
triggered
• Ensure that the data cable of the
external lithium-ion battery is
connected correctly.
• Ensure that the terminators of the
CAN bus in the communication bus
are attached.
W 953 WrnExtBMSTmOut
1
The timeout monitoring system
of the battery management has
triggered
10 Troubleshooting
SMA Solar Technology AG
Operating Manual
85
SI30M-44M-60H-80H-BE-en-33
Summary of Contents for SUNNY ISLAND 3.0M
Page 163: ......
Page 164: ...www SMA Solar com...