11. Select the parameter
BatTyp
, set the battery type as follows and confirm with
Y
.
Value
Explanation
VRLA
Lead-acid battery with immobilized electrolyte in AGM
(Absorbent Glass Mat Separator) or gel
FLA
Lead-acid battery with liquid electrolyte
LiIon_Ext-BMS
Lithium-ion battery
12. Make the following settings for lead-acid batteries.
• Select the parameter
BatVtgLst
, set the battery voltage and confirm with
Y
.
• Select the parameter
BatCpyNom
, set the C10 capacity of the battery (see the Sunny Island inverter
installation manual for how to calculate the battery capacity) and confirm the battery capacity with
Y
.
13. Make the following settings for lithium-ion batteries.
• Select the parameter
BatCpyNom
, set the C10 capacity of the battery (see the Sunny Island inverter
installation manual for how to calculate the battery capacity) and confirm the battery capacity with
Y
.
14. Select the last page and confirm the question
Setup new battery
with
Y
.
11 Cleaning and Maintenance
SMA Solar Technology AG
Operating Manual
99
SI30M-44M-60H-80H-BE-en-33
Summary of Contents for SUNNY ISLAND 3.0M