Status of the External Energy Source
0.0kW
*
1.1kW oo
67%
xx:xx:xx
------ ! M1
--- -
C
D
B
A
Figure 10: Status of the external energy source in standard mode (example)
Position
Symbol
Designation
Explanation
A
Status of the generator
Voltage and frequency of the generator are within the thresholds
set.
The maximum reverse power in the generator has been exceeded.
B
attery
Electricity generator was requested due to state of charge.
C
ycle
Generator was requested via time control.
E
xternal
Generator was requested by an extension cluster.
L
oad
Electricity generator was requested due to load.
S
tart
You have manually started the generator via Sunny Remote Con-
trol or a generator was requested via the
DigIn
input.
T
ime
You have started the generator for one hour via Sunny Re-
mote Control.
B
−
Power of the generator
or the utility grid
Power in kW
C
Generator
Generator symbol
D
Internal transfer relay
The generator is disconnected from the stand-alone grid.
The stand-alone grid is synchronized with the generator. The gener-
ator is supplying the loads and charging the battery.
5.3
User Mode
5.3.1
Pages in the User Mode
User mode displays all important information for the system sorted by category. User mode enables manual control of
the Sunny Island inverter or system devices, e.g., generator start.
5 Operation of the Sunny Island Inverter with the Sunny Remote Control
SMA Solar Technology AG
Operating Manual
29
SI30M-44M-60H-80H-BE-en-33