6
Operation of the Sunny Island Inverter with a Communication
Product
When operating a Sunny Island inverter with a communication product, observe the following differences compared
with operation via Sunny Remote Control:
• When the parameters and messages of the Sunny Island inverter are accessed via the communication product, the
defined access rights of the communication product apply (see user manual of the communication product).
• The inverter messages are displayed on the screen of the communication product as clear-text names (see
technical information "SUNNY ISLAND – Message of the same event for Speedwire (e. g. Sunny Explorer) and
RS485 / Sunny Remote Control").
Example:
The Sunny Remote Control displays the following message when the Sunny Island inverter is warning of high
operating temperatures:
W212 BatTmpHiWarn
.
The same warning message appears as clear text on the screen of the communication product:
Overtemperature fault in battery
.
• The inverter parameters are displayed on the screen of the communication product as clear-text names (see
technical information "SUNNY ISLAND – Comparison of the same parameters for
Speedwire (e. g. Sunny Explorer) and RS485 / Sunny Remote Control").
Example:
Example: The information regarding the reason for the generator request sent by the Sunny Island is displayed
on the screen of the Sunny Remote Control as parameter number and parameter name:
133.01 GnDmdSrc
.
The same information appears as clear text on the screen of the communication product:
Reason for
requesting generator
.
• A three-phase cluster is shown as a three-phase inverter on the screen of the communication product.
Function of the Sunny Island inverter in a three-
phase cluster
Display on the communication product (exam-
ple)
Master
Line conductor 1
Slave 1
Line conductor 2
Slave 2
Line conductor 3
• The parameters at the Sunny Remote Control can be adjusted only one at a time. The communication product
allows associated parameters to be grouped. To edit the parameters, this group must be selected on the
communication product.
Example:
The battery states of charge for the battery protection mode are set via three parameters on the
Sunny Remote Control:
•
223.05 BatPro1Soc
: State of charge for battery protection mode, level 1
•
223.06 BatPro2Soc
: State of charge for battery protection mode, level 2
•
223.07 BatPro3Soc
: State of charge for battery protection mode, level 3
On the communication product, all three battery states of charge can be set via the parameter
Battery state of
charge for protection mode
.
6 Operation of the Sunny Island Inverter with a Communication Product
SMA Solar Technology AG
Operating Manual
SI30M-44M-60H-80H-BE-en-33
36
Summary of Contents for SUNNY ISLAND 3.0M