8.5 Menu “PARBAT“ (3+5), Parameters Battery
This menu can only be selected after the installer password (level: 1) has been en-
tered.
Fig. 8.7:
Menu “PARBAT“ (3+5)
In the menu “PARBAT“ (3+5) the operator can change the parameters for the battery
management of the Sunny Island. In addition to the characteristic values defined by
the connected lead storage battery itself such as battery capacity, battery type and
nominal battery voltage, the settings for optimum maintenance of the capacity can be
adjusted to the plant as well (e. g. type and frequency of full charges and regularizing
charges). For more details on battery management and the required settings see
Chapter 2.2.
“PARBAT“ (3+5)
Name Description
501_Cbat nom
0 ... 10000 Ah:
Nominal battery capacity of 10 hours (C10);
Always enter value stated by manufacturer even if battery has already aged!
In case that the manufacturer did not specify a capacity of 10 hours select the
specification that is nearest to the capacity of 10 hours.
502_Bat Type
Battery type as stated by manufacturer
Gel gel
Fleece fleece
Lead-Acid liquid
electrolyte
503_Ubat nom
48 ... 60 V:
Nominal battery voltage.
504_Ubat min
40 ... 70 V:
Min. permissible battery voltage
505_Ubat max
45 ... 84 V:
Max. permissible battery voltage
506_acid density
1.1 ... 1.35 kg/l:
Nominal acid density as stated by manufacturer (only taken
into account if inverter is started via “New System“ or “New
Battery“ (see Chapter 6))