Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 115 -
SMA Regelsysteme GmbH
“PARBAT“ (3+5)
Name Description
508_Tbat Sense
Not Installed
Battery temperature sensor is not installed
Installed
Battery temperature sensor is installed
Automatically set to “Installed” in case of single-phase systems or masters in
three-phase systems. In all other cases set to “Not Installed”.
Can be set to “Installed” for slaves with additional temperature sensors in-
stalled.
509_Tbat max
30 … 55 °C:
Max. battery temperature permissible
511_Bat Fan
Battery room fan installed:
0: Not Installed
Battery room fan not installed
1: Installed
Battery room fan is installed
512_Acid Pump
Only for lead storage battery with liquid electrolyte:
0: Not Installed:
Electrolyte circulation pump is not installed
1: Installed:
Electrolyte circulation pump is installed.
By selecting “Installed“ the electrolyte circulation pump is switched on depend-
ing on the settings of parameters 513 to 516. Irrespective of the battery values,
however, there is at least one and maximum 9 circulations a day.
513_Circ time
1 ... 3600 s:
Run time of electrolyte circulation
516_Circ Qd
0.1 ... 50.0 %:
Electrolyte circulation is triggered as soon as the battery has
been charged with the corresponding ampere hours related
to its capacity (cumulative).
518_tset full
1 ... 180 d:
Time period after which full charge is to be made.
519_tset equal
7 ... 365 d:
Time period after which equalizing charge is to be made.
520_U float
2.2 ... 2.4 V:
Float charge voltage per cell
527_tcharge
1 ... 600 min:
Charging time for normal charge (with lead acid battery, see
“502_Bat Type”)
528_tcharge full
1 ... 20 h:
Charging time for full charge (with lead acid battery, see
“502_Bat Type”).
529_tcharge equal 1 ... 48 h:
Charging time for equalizing charge (with lead acid battery,
see “502_Bat Type”)
530_Ucharge
2.29 ... 2.7 V:
Charging voltage for normal charge per cell (with lead acid
battery, see “502_Bat Type”)
In case of electrolyte circulation pump installed the value should be reduced to
2.45 V. Please follow manufacturer’s instructions.
531_Ucharge full
2.25 ... 2.7 V:
Charging voltage for full charge per cell (with lead acid bat-
teries, see “502_Bat Type”)
In case of electrolyte circulation pump installed the value should be reduced to
2.45 V. Please follow manufacturer’s instructions.
532_Ucharge
equal
2.25 ... 2.7 V:
Charging voltage for equalizing charge per cell (with lead
acid battery, see “502_Bat Type”)