Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 118 -
SMA Regelsysteme GmbH
“PARGEN“ (3+6)
Name
Description
tion measures are necessary for this)
fast Mains form The Sunny Island is operated together with a grid-forming
generator and on the public utility grid. Switching takes
place without interruption (special installation measures are
necessary for this)
DroopGen
The Sunny Island is operated together with a generator ca-
pable of droop characteristics in droop mode.
DroopMains
The Sunny Island is operated together with a utility in droop
mode.
DrpGenMains
The Sunny Island is operated together with a generator ca-
pable of droop characteristics and a utility in droop mode.
BHKW-Isl-Therm Sunny Island is operated together with the ecopower CHP.
In contrast to “BHKW-Island”, the Sunny Island will not
switch off the CHP when no more electrical power is re-
quired. Thus, the ecopower CHP will be able to provide as
much thermal energy as required.
603_GenSet Interf
None:
no generator start by Sunny Island
Type 1:
Autostart, relays K1+K2
Type 2:
3 contacts run / start, relays K1, K2, K6
Type 3:
3 contacts run / Stopp, relays K1, K2, K6
EcoPower
Ecopower
CHP
(see also Fig. 12.1: Starting phase sequence for different generator types)
604_GenSet Ctrl
The Sunny Island reduces its current input in charge operation (RUN_I) ...
OFF:
... no reduction
F_MAINS:
... reduction as a function of generator frequency
I_GEN:
... as a function of generator current (converter required, see
Chapter 3.4.5)
BOTH:
... as a function of generator frequency and current (con-
verter required, see Chapter 3.4.5)
605_GenStRetr
0 ... 30:
Max. number of attempts to start the generator, before the
state “Fail Locked“ is reached (see also parameter 618). Af-
ter the minimum run-time of the generator has expired, the
counter will be reset.
606_CurTrfRatio
0 ... 1000 A per 5 A:
Current transformer ratio (in A per 5 A) for measure-
ment of generator current
607_Igen max
0 ... 500 A:
Max. generator current (per phase)
610_tGen glow
1 ... 180 s:
Length of time the relay is controlled to glow up the
generator
611_tGen crank
1 ... 60 s:
Length of time the relay is controlled to crank the generator
612_tGen warm
1 ... 900 s:
Warm-up time of generator
613_tGen minrun
1 ... 180 min:
Minimum run time of generator
614_tGen cool
1 ... 900 s:
Cooling time of generator