Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 127 -
SMA Regelsysteme GmbH
“PARREL“ (3+7)
Name Description
LOAD:
Relay is switched in relation to load (see parameter 625 to 630)
706_Man K6
as parameter 705, but for K6
707_Man K7
Operating mode of relay K7
OFF:
Switching relay K7 off
ON:
Switching relay K7 on
AUTO:
Sunny Island automatically controls relay K7.
708_Man K8
as parameter 707, but for K8
710_K1 t2 begin
0 ... 23 h:
Begin of special time period t2 for K1
711_K1 t2 end
0 ... 23 h:
End of special time period t2 for K1
712_K1 On t1
L4 ... O3:
Battery state where K1 is switched on.
713_K1 Off t1
L4 ... O3:
Battery state where K1 is switched off.
714_K1 On t2
as parameter 712, but in special time period t2
715_K1 Off t2
as parameter 713, but in special time period t2
716_K2 t2 begin
as parameter 710, but for K2
717 … 757
as above, but for K2 to K8
Table 8.6:
Settings in the menu “PARREL“ (3+7)