Parameter settings, mandatory in this configuration
The following parameters have to be set for a proper operation of the Sunny Island.
Parameter Unit
Default
Description
Master
Slaves
401_Phase Mode
1Phs_Si
ngle
Device setting
1Phs_Si
ngle (?)
3Phs_
Slv1L2
/ L3
501_Cbat nom
Ah
350
Nom. battery capacity (C10)
?
X
502_Bat Type
Lead-
Acid
Battery type
?
X
503_Ubat nom
V
60
Nom. battery voltage
60 (?)
X
504_Ubat min
V
51
Min. permissible battery voltage
51 (?)
51 (?)
505_Ubat max
V
84
Max. permissible battery voltage
81 (?)
81 (?)
706_Man K6
OFF
Operation mode of K6
AUTO
X
801_Sunny Boys
Not in-
stalled
Control method for the Sunny
Boys
Fre-
quency
(?)
Not in-
stalled
(?)
X: don’t care; ?: system-dependent; <value>(?): preferred setting, but system-dependent at last