Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 159 -
SMA Regelsysteme GmbH
Parameter settings, mandatory in this configuration
The following parameters have to be set for a proper operation of the Sunny Island.
Parameter Unit
Default
Description
Master
Slaves
401_Phase Mode
1Phs_Si
ngle
Device setting
1Phs_
Single
(?)
3Phs_
Slv1L2
/ L3
501_Cbat nom
Ah
350
Nom. battery capacity (C10)
?
X
502_Bat Type
Lead-
Acid
Battery type
?
X
503_Ubat nom
V
60
Nom. battery voltage
60 (?)
X
504_Ubat min
V
51
Min. permissible battery voltage
51 (?)
51 (?)
505_Ubat max
V
84
Max. permissible battery voltage
81 (?)
81 (?)
602_GenSet Type
None
Generator type
fast
Mains
form
(?)
None
603_GenSet Interf
None
Generator interface
Type 1
(?)
X
604_GenSet Ctrl
OFF
Generator load limiting
I_GEN
(?)
I_GEN
(?)
606_CurTrfRatio Ain/5
Aout
5
Current transformer ratio
?
?
607_Igen max
A
0
Max. generator/mains current (per
phase)
? ?
701_Man K1
OFF
Operation mode of K1
AUTO
X
702_Man K2
OFF
Operation mode of K2
AUTO
AUTO
703_Man K3
OFF
Operation mode of K3
AUTO
AUTO
704_Man K4
OFF
Operation mode of K4
AUTO
X
705_Man K5
OFF
Operation mode of K5
AUTO
X
801_Sunny Boys
Not in-
stalled
Control method for the Sunny
Boys
Fre-
quency
Not In-
stalled
X: don’t care; ?: system-dependent; <value>(?): preferred setting, but system-dependent at last