Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 166 -
SMA Regelsysteme GmbH
For a proper operation either all of the parameters „422_Ps2off“,
„423_Ps2on3off“ and „424_Ps3on“ have to be set to reasonable values,
or they all have to be left at their default values.
If only two Sunny Islands are provided in the system „424_Ps3on“ and
„423_Ps2on3off“ should be set to the same values.
Master
Slave2
Slave3
"Pconv Sum" (abs.) [kW]
"422_Ps2off" "423_Ps2on3off"
"424_Ps3on"
1.0
5.0
10.0
15.0
0
Fig. 11.7: Load-dependent en-/disabling of the additional Sunny Islands