Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 167 -
SMA Regelsysteme GmbH
Parameter settings, mandatory in this configuration
The following parameters have to be set for a proper operation of the Sunny Island.
Parameter Unit
Default
Description
Master
Slaves
401_Phase Mode
1Phs_Si
ngle
Device setting
1Phs_M
str3 (?)
1Phs_
Slv2 / 3
501_Cbat nom
Ah
350
Nom. battery capacity (C10)
?
X
502_Bat Type
Lead-
Acid
Battery type
?
X
503_Ubat nom
V
60
Nom. battery voltage
60 (?)
X
504_Ubat min
V
51
Min. permissible battery voltage
51 (?)
51 (?)
505_Ubat max
V
84
Max. permissible battery voltage
81 (?)
81 (?)
602_GenSet Type
None
Generator type
fast Grid
form (?)
None
603_GenSet Interf
None
Generator control method
Type 1
(?)
X
701_Man K1
OFF
Operating mode of K1
AUTO
X
702_Man K2
OFF
Operating mode of K2
AUTO
AUTO
X: don’t care; ?: system-dependent; <value>(?): preferred setting, but system-dependent at last