Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 170 -
SMA Regelsysteme GmbH
Parameter settings, mandatory in this configuration
The following parameters have to be set for a proper operation of the Sunny Island.
The term “cluster1” refers to the cluster that is meant for controlling the generator (if
existing).
Parameter Unit
Default
Description
Masters
Slaves
401_Phase Mode
1Phs_Si
ngle
Device setting
3Phs_Mstr1
Set
3Phs_Slv1
L2 / L3
501_Cbat nom
Ah
350
Nom. battery capacity (C10)
?
X
502_Bat Type
Lead-
Acid
Battery type
?
X
503_Ubat nom
V
60
Nom. battery voltage
60 ( ?)
X
504_Ubat min
V
51
Min. permissible battery voltage
51 ( ?)
51 (?)
505_Ubat max
V
84
Max. permissible battery voltage
81 (?)
81 (?)
601_GenSet Oper
Auto
Generator control method
Cluster1:
Auto
Cluster2:
Man. Stop
X
602_GenSet Type
None
Generator type
DroopGen DroopGen
603_GenSet Ctrl
OFF
Control interface for the genera-
tor
Type 1 (?)
X
647_ClustMode
Off
Function to be fulfilled in a two
cluster configuration
Cluster1:
SupMstr
Cluster2:
ClstMstr
Slave2:
Reptr
Slave3
:
Off
X: don’t care; ?: system-dependent; <value>(?): preferred setting, but system-dependent at last