Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 195 -
SMA Regelsysteme GmbH
„PARALL“ (3+9)
Parameter Unit
Min.
Max.
Default
Description
424_Ps3on
(D)
kW
0
16
0,00
Relates to two/three Sunny Island in parallel con-
figurations (see Chapter 11.6.1): If the cumulative
load on all Sunny Islands raises above this value,
the Slave3 Sunny Island will be activated
If one of the parameters 422, 423 or 424 is set to a
value different from 0.00, all these parameters
have to be set to reasonable values.
In a system where no Slave3 is present, the setting
of this parameter should be equal to the setting of
“423_Ps2on3off”
425_SlvTimeHyst
(D)
s
0
240
0
Relates to two/three Sunny Island in parallel con-
figurations (see Chapter 11.6.1): Delay before a
Slave goes idle after a corresponding condition oc-
cured (cf. 422_Ps2off and 423_Ps2on3off)
426_RevCurrent
(A)
A
0
200
0
If the current that flows into the grid/generator ex-
ceeds this value, it is interpreted as grid/generator
failure and the Sunny Island will throw off the
grid/generator. This mechanism is only active
when "602_GenSet Type" is set to DroopMains or
DroopMainsForm and mains is active.
0: Reverse current detection inactive
501_Cbat nom
(A)
Ah
100 10000
350
Nominal battery capacity of 10 hours (C10); always
enter the value stated by the manufacturer even if
the battery has already aged!
502_Bat Type
(A)
0
2
2
Battery type as stated by manufacturer
0: Gel
gel
1: Fleece
fleece
2: Lead-Acid
liquid electrolyte
503_Ubat nom
(A)
V
48
60
60
Nominal battery voltage.
504_Ubat min
(A)
V
40
70
51
min. battery voltage permissible
505_Ubat max
(A)
V
45
84
84
max. battery voltage permissible
506_acid density
(A)
kg/l
1,1
1,35
1,24
Nominal acid density according to manufacturer
(only taken into account if inverter is started via
“New System“ or “New Battery“ (see Chapter 6))