Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 198 -
SMA Regelsysteme GmbH
„PARALL“ (3+9)
Parameter Unit
Min.
Max.
Default
Description
535_State StopT
(C)
0
10
2
In case of deep-cycle discharge the device will
switch off to reduce strain on the battery, if no
charging current of a minimum of 1 A flows into the
battery for more than 5 minutes within the defined
time period (see also “533_Stdby t beg”,
„534_Stdby t end“).
The low battery load mode is always activated,
when one battery state lower is reached.
However from 6 am to 6 pm the Sunny Island at-
tempts to switch on every four hours.
Battery state when the low battery load mode is
activated:
0: L4
1: L3
2: L2
3: L1
4: N4
5: N3
6: N2
7: N1
8: O1
9: O2
10: O3
536_Fan on del
(A)
min
0
1440
1
Delay of switch-on for battery room fan
In order to use this setting, “511_Bat Fan” must be
set to “Installed“
537_Fan off del
(A)
min
0
360
60
Delay of switch-off for battery room fan
In order to use this setting, “511_Bat Fan” must be
set to “Installed“
538_Iloss nom
(A)
mA
/100
Ah
0
-100
-30
Specific leakage current of battery for float charge
and 20 °C
Approximate values:
-30 mA/100Ah for new batteries
-80 mA/100Ah for batteries that have considerably
aged
The value is NOT automatically defined by the
Sunny Island. Battery management can therefore
be further optimized by manually adjusting the
value from time to time.
539_LineResist
(A)
mOh
ms
0
500
0.000
Resistance of the battery (DC) cable