Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 201 -
SMA Regelsysteme GmbH
„PARALL“ (3+9)
Parameter Unit
Min.
Max.
Default
Description
607_Igen max
(A)
A
0
500
0
Max. generator current (per phase),
only applies if “604_GenSet Ctrl” is set accordingly
608_tGen switch
(D)
msec -40
+40
-10
Time to compensate the tripping time of the Sunny
Island’s contactor (SIBPRETR).
The optimized value will NOT exactly equal the
tripping time of the contactor!
610_tGen glow
(C)
s
1
180
15
Length of time the relay is controlled to glow up the
generator
611_tGen crank
(C)
s
1
60
10
Length of time the relay is controlled to crank the
generator
612_tGen warm
(C)
s
1
900
15
Warm-up time of generator
613_tGen minrun
(C)
min
1
180
5
Minimum run time of generator
614_tGen cool
(C)
s
0
900
60
Cooling time of generator
615_tGen stop
(C)
s
1
900
10
Length of time the relay is controlled to stop the
generator
616_tGen lock
(C)
min
1
180
5
Period of time the generator – after having been
stopp–d – cannot be restarted via the Sunny Island
(can be shortened by confirmation in the
“GENSET“ (2-2) menu)
617_tGen fail
(C)
min
1
180
5
Period of time the generator cannot be restarted
via the Sunny Island after a generator failure (can
be shortened by confirmation in the “GENSET“ (2-
2) menu)
618_tGen faillock
(C)
h
1
168
6
Period of time the generator cannot be restarted
via the Sunny Island after a certain number of fail-
ures as defined in “605_GenStRetr“ has occurred
during start-up (can be shortened by confirmation
in the “GENSET“ (2-2) menu)