Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 203 -
SMA Regelsysteme GmbH
„PARALL“ (3+9)
Parameter Unit
Min.
Max.
Default
Description
633_PConsMin
(A)
W 0
2000
1000
Lower limit for the load power (cumulative power
averaged over all three phases within the time pe-
riod of the parameter “630_TavgLdSum“), that has
to be exceeded, in order to start the Ecopower
CHP even in the case of charging states between
“631_PldLzMin” and “632_PldLzMax“.
634_PConsMax
(A)
W 0
10000
3000
Upper limit for the load power (cumulative power
averaged over all three phases within the time pe-
riod of the parameter), when the Ecopower CHP
will already be started in the case of a charging
state of “632_PldLzMax”.
635_PChargeMax
(A)
W 0
16000
3000
Setpoint for the charging power, that the Sunny
Island obtains from the Ecopower CHP.
636_PDump1
(A)
W 0
8000
500
Power of Dumpload 1, that has to be connected to
the relay K1 of the Sunny Island during the opera-
tion with the Ecopower CHP. (“701_Man K1“ = Au-
to)
637_PDump2
(A)
W 0
8000
2000
Power of Dumpload 2, that has to be connected to
the relay K6 of the Sunny Island during the opera-
tion with the Ecopower CHP. (“706_Man K6“ = Au-
to)
638_PBHKWMin
(A)
W 0
4000
2200
Minimum power of the Ecopower CHP
639_PBHKWMax
(A)
W 0
10000
4700
Maximum power of the Ecopower CHP
640_BHKW_ton
(A)
s
0
10000
300
Minimum run-time of the ecopower CHP
641_BHKW_toff
(A)
s
0
10000
300
Minimum pause time of the ecopower CHP
642_BHKW_tmax
(A)
s
0
20000
0
Maximum run-time of the ecopower CHP in mode
2 (fast control)
0: No limitation
644_PldOnLx
(A)
W 0
4700
0
The ecopower CHP will be activated when this
load has been exceeded on one of the phases
0: No load dependent activation
645_RevPower
(A)
kW -100
100
-0,5
Generator reverse power protection:
If the power delivered by the generator falls below
this value, the generator will be disconnected
646_PDump3
(A)
W
0
8000
4500
Power of Dumpload 3, that has to be connected to
the relay K2 of the Sunny Island during the opera-
tion with the Ecopower CHP. (“702_Man K2“ = Au-
to)