Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 213 -
SMA Regelsysteme GmbH
Name Unit
Min.
Max.
Default
Description
GenFail
0
6
0
Generator failure state
0: none
no failure
1: F_crank
failure during cranking
2: F_warm
failure during warming up
3: F_Run
failure in operation
4: F_Runlim
limitation violation of generator
frequency, voltage or reverse
power
5: F_Cool
failure during cooling down
6: F_Stop
failure during stop (could not be
stopped)
K1 State
0
1
0
State of relay
0: off
1: on
K2 State
0
1
0
State of relay
K3 State
0
1
0
State of relay
K4 State
0
1
0
State of relay
K5 State
0
1
0
State of relay
K6 State
0
1
0
State of relay
K7 State
0
1
0
State of relay
K8 State
0
1
0
State of relay
SB Step
%
-100
100
0
Current step size for Sunny Boy power limitation
(via COM2)
Fext
Hz
0
100
0
Current grid frequency on Generator / Mains sync.
input
Uext eff
V
0
500
0
RMS value of synchronous voltage
Iext eff
A
0
500
0
Current generator current (from converter)
Pext
kW
-320
320
0
Current generator active power
If an “ecopower Mini-BHKW” is installed this
equals the power of the CHP unit, as received
from by the Sunny Island on its COM3 port.
Ubat mean
V
0
200
0
Mean value of battery voltage
Ibat mean
A
-150
150
0
Mean value of battery current
Pbat mean
W
-32000 32000
0
Mean value of battery power
Tbat mean
degC
-25
125
0
Mean value of battery temperature
Uzw Cuk mean
V
0
500
0
Mean value of the intermediate circuit voltage
Fconv
Hz
0
100
0
Current grid frequency
Uconv eff
V
0
500
0
Current grid voltage actual value
Iconv eff
A
0
320
0
RMS value of grid current
Pconv
W
-32000 32000
0
Grid active power Sunny Island
Sconv
VA
-32000 32000
0
Grid apparent power SI
Qconv
var
-32000 32000
0
Grid reactive power SI
Uchrg act
V
0
200
0
Setpoint value of battery voltage