Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 214 -
SMA Regelsysteme GmbH
Name Unit
Min.
Max.
Default
Description
SOC diff RSK
%
0
100
0
Estimated error of “SOC RSK”
Cbat act
Ah
50
10000
100
Current battery capacity
SOC diff AHB
%
0
100
50
Error of state of charge for full charge calibration
Qdn full
Ah/
100Ah
-10000 10000
0
Charge throughput (discharge) since last full
charge
Qdn equal
Ah/
100Ah
-10000 10000
0
Charge throughput (discharge) since last equaliz-
ing charge
tpast full
d
0
3700
0
Time since last full charge
tpast equal
d
0
3700
0
Time since last equalizing charge
t Uconst chg
h
0
10
0
Time of constant U Phase for normal charges
t Uconst full
h
0
20
0
Time of constant U phase for full charges
t Uconst equal
h
Time of constant U phase for equalizing charges
Qd float
Ah/
100Ah
-100
0
0
Charge taken out since beginning of float charge
ChargeOper
0
5
1
State of battery management (charging methods)
1: none
(required charge voltage for
battery management)
2: normal
(normal charge)
3: full
(full charge)
4: float
(float charge)
5: equalize
(equalizing charge)
SOC diff
%
0
100
50
Difference of state of charge calculation
SOC AHG
%
-100
110
50
Charge degree for full charge calibration
SOC RSK
%
-100
110
50
Charge degree of module for open-circuit voltage
calibration
Name Unit
Min.
Max.
Default
Description
“DATBAT“ (1+3)
Bat State
0
10
0
Current battery state
0: L4
deep-cycle discharge
1: L3
2: L2
3: L1
4: N4
5: N3
6: N2
7: N1
battery full
8: O1
overcharge
9: O2
10: O3
SOC act
%
-100
110
0
Actual battery state of charge
Ubat mean
V
0
200
0
Mean value of battery voltage