Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 34 -
SMA Regelsysteme GmbH
Please note the following points in any case for the installation of the Sunny
Island:
•
The mounting background must be firm (weight of Sunny Island
4500 approx. 45 kg).
•
The ambient temperature must be between -25 °C and +45 °C.
•
If the Sunny Island is transferred from a cold to a warm place,
wait for a sufficient time (at least 15 minutes) before commis-
sioning so that any moisture condensation that might have oc-
curred can evaporate.
•
A minimum clearance of 20 cm must be available above the
Sunny Island for ventilation, i.e. no installation in cabinets with-
out ventilation, no installation directly under ceiling, etc.
•
The free air circulation around the case must not be obstructed
to ensure sufficient cooling.
•
If you install the Sunny Island in a cabinet or closet etc., the air
circulation must be sufficient for heat dissipation - provide ex-
ternal ventilation.
•
The heat sink can reach a temperature of more than 80
o
C.
•
Provide a correct position of the battery inverter (see Fig. 3.1
and Fig. 3.2).