Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 47 -
SMA Regelsysteme GmbH
3.4.3 Connection of Battery Temperature Sensor
A PT 100 sensor with four-wire technology is required to measure the battery tem-
perature. The sensor is connected to the inverter at the terminals X1:1-X1:4 (Fig.
3.6).
If the temperature sensor is to be connected with a shielded cable, connect the
shielding to terminal X1:5. This terminal is connected to the case and thus to the PE
connections of the inverter. Therefore make absolutely sure to avoid creating any
electric bond by attaching the temperature sensor to the battery.
1
2
3
4
5
Sunny Island
X1:
PT 100
Battery
temperature
Fig. 3.6:
Connection of a temperature sensor
To protect the battery always connect a battery temperature sensor
(the Sunny Island displays a failure if no sensor is installed).
In configurations with more than one Sunny Island per battery only
the master Sunny Island needs to be equipped with a battery tem-
perature sensor.