Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 90 -
SMA Regelsysteme GmbH
Parameter Default
Description
705_Man K5
OFF
Operating mode of relay K5
OFF:
Switch relay K5 off
ON:
Switch relay K5 on
AUTO:
Sunny Island automatically controls relay K5.
RUN:
Relay is only switched on when the Sunny Is-
land operates.
RUN_U:
Relay is only switched on when the Sunny Is-
land operates as the grid–forming element.
RUN_I:
Relay is only switched on when the Sunny Is-
land is in “grid-tied operation“.
HD_CTRL:
Relay is switched on during transfer from grid-
forming to grid-tied operation.
TK_CTRL:
Relay is switched on during transfer from grid-
tied to grid-forming operation.
HDTK_CTRL:
Relay is switched on during any transfer from
grid-tied to grid-forming operation or vice
versa.
GEN_MANU:
Relay is switched on if generator has already
been started before the Sunny Island.
LOAD:
Relay is switched on in relation to load (see
also parameter 625 to 630)
706_Man K6
OFF
Operating mode of relay K6 (for details see 705)
707_Man K7
OFF
Operating mode of relay K7 (for details see 701)
708_Man K8
OFF
Operating mode of relay K8 (for details see 701)
712_K1 On t1
N4
When this battery state is reached, K1 is switched on.
(see Chapter 2.2.2)
713_K1 Off t1
N1
When this battery state is reached, K1 is switched off.
(see Chapter 2.2.2)
801_Sunny Boys Not installed
Not installed:
Sunny Island is not to control Sunny Boys.
Installed:
Sunny Island is to control Sunny Boys (via
COM2)
Inst. Mains:
Sunny Island only is to control Sunny Boys if
grid feeding is not possible (via COM2)
Frequency
Sunny Island controls the Sunny Boys via grid
frequency (depending on the Sunny Boy’s
firmware) in operation mode RUN_U
Table 6.1:
Parameters to be entered for configuration via “New Sys MASTER“