Sunny Island 4500
Installation & Operating Instructions
BWRI45-13-EE0304
- 93 -
SMA Regelsysteme GmbH
401_Phase
Mode
1Phs_Single
1Phs_Single:
single-phase operation, inverter is the only device
1Phs_Psingle:
single-phase parallel operation with one battery per
device
(grid and generator not possible!)
1Phs_Mstr2:
single-phase parallel operation with two devices
with one single battery pack, device is master
1Phs_Mstr3:
single-phase parallel operation with three devices
with one single battery pack, device is master
1Phs_Slv2:
single-phase parallel operation with two or three
devices with one single battery pack, device is
slave 2
1Phs_Slv3:
single-phase parallel operation with three devices
with one single battery pack, device is slave 3
3Phs_Mstr1Set: three-phase operation, device is master (L1)
3Phs_parallel: three-phase operation in droop-mode (see Chapter
11.7.2 and 11.7.3), device is master (L1)
3Phs_Slv1L2:
three-phase operation, device is slave (L2)
3Phs_Slv1L3:
three-phase operation, device is slave (L3)
647_ClustM
ode
Off
Off:
No special function is assigned to this Sunny Is-
land
SupMstr:
Sunny Island is the “Super Master” that is in
charge of controlling the other clusters in the sys-
tem and the generator, where applicable.
ClstMstr:
Sunny Island is the Master of a secondary cluster
in the system that is controlled by a “Super Mas-
ter”
Reptr:
Sunny Island is the Slave to which COM2 port
another cluster is connected??
504_Ubat
min
51 V
min. battery voltage permissible
505_Ubat
max
84 V
max. battery voltage permissible
604_GenSet
Ctrl
OFF
The Sunny Island reduces its current input in charge operation
(RUN_I) ……
OFF:
... not at all
F_MAINS:
... as a function of generator frequency (see
“407_Fext nom”)
I_GEN:
... as a function of generator current (converter re-
quired, see Chapter 3.4.5)
BOTH:
... as a function of generator frequency (see
“407_Fext nom”) and current (converter required,
see Chapter 3.4.5)
606_CurTrfR
atio
5 A/5A
Current transformer ratio (in A per 5 A) for measurement of generator
current
702_Man K2
OFF
Operating mode of relay K2 (for details see 701)
703_Man K3
OFF
Operating mode of relay K3 (for details see 701)
Table 6.2:
Parameters to be entered for configuration via “New Sys SLAVE“