14.3 Generator and Grid
In addition to the utility grid, a generator can also be integrated into an off-grid system as a secondary
protective measure. This is particularly useful in case of long-term grid failures, even if the battery
capacity is no longer sufficient to bridge the failure after a period of time.
The common solution in such cases is using a transfer switch which can be purchased as a manual or
automatic switch. By using such a switch, a diesel generator is connected to the AC2 connection to
which the utility grid is normally connected, as displayed in the figure below:
To use such a switch, carry out the installation as follows.
The requirements of the generator and the utility grid demand different settings of the Sunny Island.
In a backup system with generator, the Sunny Island needs a signal circuit via the DigIn input.
The DigIn input notifies the Sunny Island when the utility grid is feeding in.
Abrupt switching from the utility grid to the generator and vice versa can lead to the destruction of
the Sunny Island.
• If an automatic switch is installed, make sure that it completely disconnects the Sunny Island
from the grid and from the generator for at least five seconds.
• If a manual switch is installed, leave the switch in the OFF position for at least five seconds
before switching to the new position.
• If no switch is installed, install a switch. Refer to the download area at
www.SMA-America.com for further information on how to install a switch for connecting the
Sunny Island to the utility grid and to a generator.