19 Parameter Lists
SMA America, LLC
162
SI4548_6048-US-TB_en-13
Technical description
133# Generator State
No. Name
Description
Value clear text
(No.)
Explanation
01
GnDmdSrc
Source for
generator request
None (1)
No request
Bat (2)
State-dependent battery
charging
Lod (3)
Load-dependent
Tim (4)
Time-controlled
Run1h (5)
Requested for 1 hour
Start (6)
Manually started
ExtSrcReq (7)
Requested via an external
source
02
GnStt
Generator state
Off (1)
Off
Init (2)
Init
Ready (3)
Waiting for request (ready)
Warm (4)
Warming up
Connect (5)
Connecting
Run (6)
Operation
Retry (7)
Restarting
Disconnect (8)
Disconnecting
Cool (9)
Cooling down
Lock (10)
Locked after error
Fail (11)
Error
FailLock (12)
Locked after error occurred.
03
GnRmgTm
Remaining time of
the generator
(minimum run time)
in hours, minutes
and seconds
04
GnRnStt
Status generator
feedback on the
master
Off (1)
off
On (2)
on