#223 Battery Protection
12
AutoEquChrgEn
a
Automatic
equalization
charge
Disable
Disable
Enable
Enable
Enable
No. Name
Description
Value
Default value
01
BatPro1TmStr
Starting time of the
battery-preservatio
n mode (level 1)
22:00:00
02
BatPro1TmStp
End time of
battery-preservatio
n mode (level 1)
06:00:00
03
BatPro2TmStr
Starting time of the
battery-preservatio
n mode (level 2)
17:00:00
04
BatPro2TmStp
End time of
battery-preservatio
n mode (level 2)
09:00:00
05
BatPro1Soc
Battery state of
charge for
preservation mode
level 1
0% to 70%
20%
06
BatPro2Soc
Battery state of
charge for
preservation mode
level 2
0% to 70%
15%
07
BatPro3Soc
Battery state of
charge for
preservation mode
level 3
0% to 70%
10%
No. Name
Description
Value
Explanation
Default
value