19 Parameter Lists
SMA America, LLC
172
SI4548_6048-US-TB_en-13
Technical description
07
GdVldTm
Minimum time
required for grid
(voltage and
frequency) to be
within permissible
range for
connection
300 sec
08
GdMod
Grid interface
GridCharge
Charging on the
grid
GdFeed
GridFeed
Charging and
backfeed on the
grid
09
GdRvPwr
Permissible grid
reverse power
(active power)
0 W to 5,000 W
100 W
10
GdRvTm
Permissible time for
grid reverse power
0 sec to 60 sec
5 sec
15
GdAlSns
AI sensitivity
Low
Low
Normal
Medium
Medium
Normal
Normal
High
High
37
GdVtgIncProEna Voltage increase
protection
Disable
Disable
Disable
Enable
Enable
38
GdVtgIncPro
Boundary for
voltage increase
protection
132 V
41
GdSocEna
Activate the grid
request based on
SOC
Disable
Disable
Disable
Enable
Enable
42
GdPwrEna
Activate the grid
request based on
power
Disable
Disable
Disable
Enable
Enable
No. Name
Description
Value
Explanation
Default
value