SMA America, LLC
20 Troubleshooting
Technical description
SI4548_6048-US-TB_en-13
209
20.6.6 Category SYS
20.7 Failure Categories
The Sunny Island distinguishes between five different levels of errors, each requiring different user
interaction:
Display no.
Description
E705
Device start
E706
Date, time changed
E707
New system configured in QCG
E708
Part 1 of firmware updated
E709
Part 2 of firmware updated
E710
Cluster firmware updated
E711
MMC/SD card inserted
E712
Parameters from MMC/SD card loaded
E851
Sunny Island Charger #1 detected
E852
Sunny Island Charger #2 detected
E853
Sunny Island Charger #3 detected
E854
Sunny Island Charger #4 detected
Level
Designation
Display
Meaning
1
Warning
Warning
Warning, device continues to run. There is an explicit
information on the "Home Screen" that a warning
was recorded.
2
Malfunction 1 Malfunction
Failure that can only be detected during operation.
Device switches off. Device can be restarted
immediately (autostart).
3
Malfunction 2 Malfunction
Failure that can also be detected in standby mode.
Device switches off. The device can only be restarted
(autostart) once the system detects that the
malfunction has ended.
4
Error
Failure
Device error, device switches off. User interaction
required (failure removal, confirmation, manual
restart).
5
Device defect Defect
Device is defect. Device switches off and does not
switch on again. Permanent operation inhibition
Device must be replaced.
Summary of Contents for Sunny Island 4548-US
Page 2: ......
Page 14: ......
Page 240: ...www SMA Solar com SMA Solar Technology SMA America LLC www SMA America com...