8 Initial Start-Up
SMA America, LLC
70
SI4548_6048-US-TB_en-13
Technical description
GenGrid:
– Maximum generator current (0 A to 224 A), default setting: "30 A"
– Generator interface (Manual, GenMan, Autostart), default setting: "Autostart"
– Maximum grid current (0 A to 224 A), default setting: "30 A"
Grid:
– Maximum grid current (0 A to 224 A), default setting: "30 A"
Gen:
– Maximum generator current (0 A to 224 A), default setting: "30 A"
– Generator interface (Manual, GenMan, Autostart), default setting: "Autostart"
4. The following parameters must be set when
"New Battery"
is selected:
– Battery type (VRLA, FLA, NiCd), default setting: "VRLA"
– Nominal voltage of the battery (42 V to 52 V in 2 V steps for FLA and VRLA, 43.2 V to 48 V
in 1.2 V steps for NiCd), default setting: "48.0 V"
– Nominal capacity of the battery (100 Ah to 10000 Ah), default setting: "100 Ah"
☑ After entering all parameters, the following
notification appears.
5. Press <ENTER> to confirm.
☑ The notification shown here is displayed.
6. Press <ENTER> and hold until you hear a beep.
☑ The Sunny Island has started and is in operation.
GenGrid
Grid Backup with Generator
Adjustable parameters
Observe the information on the possible settings of the parameters (see Section 19 "Parameter
Lists", page 157).
Note that some parameters can only be changed after entering the installer password
(see Section 10.5 "Entering the Installer Password", page 86) and in standby mode
(see Section 9.2 "Stopping the Sunny Island (Standby)", page 74).
Value in variable
Explanation